Kylaggregat / Tak
For ceiling mounting
300W - 4000W | IP54
Ceiling-mounted cooling units with cooling capacity from 300 to 6000 W for effective temperature control in control cabinets.
The unit has a double cooling fin, built-in hot-pipe for evaporation of condensation water and a protective shutdown in case of flooding of the condensation tray, with a visual alarm as standard.
Specification
| Article: | Kylaggregat / Tak |
|---|---|
| Category: | Cooling Units |
| Brand: | DKC |
| Protection class: | IP54 |
| Voltage: | 230V | 400/440V |
| Effect: | 300W - 4000W |
| Operating temperature: | 20°C - 50°C | 20°C - 55°C (UL) |
| Material: | Steel sheet | Stainless steel AISI304L | Acid-resistant AISI316L (on request) |
| Color: | RAL 7035 (steel sheet) |
Do you need a price & more information?

Product description
Cooling unit / Ceiling for ceiling mounting, with a power from 300W-6000W. The units have double cooling fins and visual alarm as standard. Filter grids and filter mats are not included. The cooling units have a built-in "hot-pipe" loop that evaporates the condensation water from the collection tray. If the condensation tray overflows, the cooling unit is switched off.
- The cooling units are also available with UL certification.
Top version:
- 2 PLUG-IN connectors for power supply
- Control with alarm for overtemperature
- Remote ON/OFF (door contact switch)
- RS485 serial interface for remote control (ordered separately)
Other:
- Foamed polyurethane gasket on the back of the unit.
- Built-in "hot-pipe" loop in the condensate tray that evaporates the condensate water.
- Protective shut-off in case of flooding of troughs.
- External washable air filter.
- Texture coated in RAL7035.
- Other RAL colors are available.
- Visual alarm.
- RS485 serial protocol is available on request.
- Other voltage possible.
Drawing
Article number
| Art.No | Name | Version | Capacity | Input voltage AC | Operating temperature: | Width mm | Height mm | Depth mm | Protection class | Color / Material (housing) | |
|---|---|---|---|---|---|---|---|---|---|---|---|
| R5CND05021RT | Cooling unit Roof | Top | 500W | 230V | 20°C-50°C | 570 | 305 | 300 | IP54 | RAL7035 | |
| RICND05021RT | Cooling unit Roof | INOX | Top | 500W | 230V | 20°C-50°C | 570 | 305 | 300 | IP54 | AISI304L | |
| R5CND08021RT | Cooling unit Roof | Top | 800W | 230V | 20°C-50°C | 600 | 305 | 405 | IP54 | RAL7035 | |
| RICND08021RT | Cooling unit Roof | INOX | Top | 800W | 230V | 20°C-50°C | 600 | 305 | 405 | IP54 | AISI304L | |
| R5ULK08021R | Cooling unit Roof | Top UL | 800W | 230V | 20°C-55°C | 600 | 305 | 405 | IP54 | RAL7035 | |
| RIULK08021R | Cooling unit Roof | INOX | Top UL | 800W | 230V | 20°C-55°C | 600 | 305 | 405 | IP54 | AISI304L | |
| R5CND10021RT | Cooling unit Roof | Top | 1000W | 230V | 20°C-50°C | 600 | 305 | 405 | IP54 | RAL7035 | |
| RICND10021RT | Cooling unit Roof | INOX | Top | 1000W | 230V | 20°C-50°C | 600 | 305 | 405 | IP54 | AISI304L | |
| R5ULK10021R | Cooling unit Roof | Top UL | 1000W | 230V | 20°C-55°C | 600 | 305 | 405 | IP54 | RAL7035 | |
| RIULK10021R | Cooling unit Roof | INOX | Top UL | 1000W | 230V | 20°C-55°C | 600 | 305 | 405 | IP54 | AISI304L | |
| R5CND15021RT | Cooling unit Roof | Top | 1500W | 230V | 20°C-50°C | 600 | 455 | 405 | IP54 | RAL7035 | |
| RICND15021RT | Cooling unit Roof | INOX | Top | 1500W | 230V | 20°C-50°C | 600 | 455 | 405 | IP54 | AISI304L | |
| R5ULK17021R | Cooling unit Roof | Top UL | 1500W | 230V | 20°C-55°C | 600 | 455 | 405 | IP54 | RAL7035 | |
| RIULK17021R | Cooling unit Roof | INOX | Top UL | 1500W | 230V | 20°C-55°C | 600 | 455 | 405 | IP54 | AISI304L | |
| R5CND20021RT | Cooling unit Roof | Top | 2000W | 230V | 20°C-50°C | 600 | 455 | 405 | IP54 | RAL7035 | |
| RICND20021RT | Cooling unit Roof | INOX | Top | 2000W | 230V | 20°C-50°C | 600 | 455 | 405 | IP54 | AISI304L | |
| R5CND20043RT | Cooling unit Roof | Top | 2000W | 400/440V 3-phase | 20°C-50°C | 600 | 455 | 405 | IP54 | RAL7035 | |
| RICND20043RT | Cooling unit Roof | INOX | Top | 2000W | 400/440V 3-phase | 20°C-50°C | 600 | 455 | 405 | IP54 | AISI304L | |
| R5CND30043RT | Cooling unit Roof | Top | 3000W | 400/440V 3-phase | 20°C-50°C | 800 | 505 | 495 | IP54 | RAL7035 | |
| RICND30043RT | Cooling unit Roof | INOX | Top | 3000W | 400/440V 3-phase | 20°C-50°C | 800 | 505 | 495 | IP54 | AISI304L | |
| R5CND40043RT | Cooling unit Roof | Top | 4000W | 400/440V 3-phase | 20°C-50°C | 800 | 505 | 495 | IP54 | RAL7035 | |
| RICND40043RT | Cooling unit Roof | INOX | Top | 4000W | 400/440V 3-phase | 20°C-50°C | 800 | 505 | 495 | IP54 | AISI304L |
Accessories
Video
Document
You may also need...
Cable duct slotted halogen-free in U43X
Floor cabinet
Stainless steel AISI304L & AISI316L
Door & Back Panel | IP55
Floor cabinet
Door & Back Panel | IP55
Slim design, high performance for control and automation cabinets
Output current 3.4 to 40A | Efficiency up to 93% | AC input voltage | Screw terminal
Panel-mounted power meters with MID certification for billing and advanced power quality analysis
Do you need help choosing the right solution?
Choosing components is often about more than dimensions and threads.
Material choice, seals, IP class and environmental requirements affect both function and lifespan.
If you are unsure, we are happy to help you ensure that the solution works in your application.